I'm Steve Bauer with Bauer inspections and on this house on this electrical panel we found a breaker that's double loved double logged or double tapped there's two wires under one screw that is not acceptable so I've turned the power off to this circuit and it really doesn't matter what they go to it's not correct so people often ask me what does it go to when I find that and the fact is it just doesn't matter there's no way that it's acceptable so with the power off to this breaker we shake the breaker out and we unscrew the two wires and now we're going to replace this breaker that had two wires to it with this breaker that has accommodation for two wires so they're on two separate circuits and with these turned off we'll put one of the wires in here and tighten it down and and take the other wire here put it in the other side some of you that might want to try this if you're not as comfortable around electricity as I am you might want to turn the main breaker off here so none of this is electrified but I personally don't have any problem doing that and then I'm on it with this still off and these tight I put the breaker back in there push it in and now we have eliminated the double lugging with two individual circuits you you